ARI STANDARD 210 / 240-89

TABLE 3
Operating Conditions for Standard Rating and Performance Tests Using Appendix A
TEST INDOOR UNIT OUTDOOR UNIT
Air
Entering
Air
Entering
DB
F
WB
F
DB
F
WB
F
C
O
O
L
I
N
G
Standard Rating Conditions
"A" Cooling Steady State1
80 67 95 752
"B" Cooling Steady State 80 67 82 652
"C" Cooling Steady State
Dry Coil
80 575 82 652
"D" Cooling Cyclic
Dry Coil
80 575 82 652
Low Temperature Operation
Cooling
67 57 67 572
Insulation Efficiency 80 75 80 752
Condensate Disposal
80 75 80 752
Maximum Operating Conditions 80 67 115 752
H
E
A
T
I
N
G
Standard Rating Conditions
High Temperature Heating3
Steady State
70 60
(max)
47 43
High Temperature Heating
Cyclic
70 60
(max)
47 43
High Temperature Heating4
70 60
(max)
62 56.5
Low Temperature Heating
Steady State
70 60
(max)
17 15
Frost Accumulation 70 60(max) 35 33
Maximum Operating Conditions
80 - 75 65
No Footnotes Applicable to This Table
1. Same conditions used for Voltage Tolerance Tests.
2. The wet bulb temperature condition is not required when testing air-cooled condensers which do not evaporate condensate.
3. Same conditions used for Voltage Tolerance Tests (Heating-only units).
4. For two speed, two compressor or units with compressor unloading capability.
5. Wet bulb sufficiently low that no condensate forms on evaporator.

Table 3 is reprinted from page 4 of the 1989 Standard for Unitary Air-Conditioning and Air-Source Heat Pump Equipment Standard 210/240, ARI, courtesy of the Air-Conditioning & Refrigeration Institute (ARI).


TABLE 4
Operating Conditions for Standard Rating and Performance of Variable
Equipment Meeting the Requirements of Appendix A
TEST INDOOR UNIT OUTDOOR UNIT
Air Entering Air Entering
DB
F
WB
F
DB
F
WB
F
"A" Cooling Steady State
At Maximum (k=2) Compressor Speed
80 67 95 751
"B" Cooling Steady State
At Maximum (k=2) Compressor Speed
80 67 82 651
"B-1" Cooling Steady State
At Minimum (k=1) Compressor Speed
80 67 82 651
Low Ambient Cooling Steady State
At Minimum (k=1) Compressor Speed
80 67 67 53.51
Dry Coil Cooling Steady State
At Minimum (k=1) Compressor Speed
80 574 67 53.51
Cyclic Cooling Steady State4
At Minimum (k=1) Compressor Speed
80 574 67 53.51
Intermediate Cooling Steady State
At Intermediate (k=i) Compressor Speed
80 67 87 691
Standard Rating - Heating
At Normal2 (k=n) Compressor Speed
70 60
(max)
47 43
Max Temperature Heating
At Minimum (k=1) Compressor Speed
70 60 62 56.5
Cyclic Heating4
At Minimum (k=2) Compressor Speed
70 60 62 56.5
High Temperature Heating
At Maximum (k=2) Compressor Speed
70 60 47 43
High Temperature Heating
At Minimum (k=1) Compressor Speed
70 60 47 43
Frost Accumulation3At Maximum (k=2)
and/or Intermediate (k=i) Compressor Speed
70 60 35 33
Low Temperature Heating
At Maximum (k=2) Compressor Speed
70 60 17 15
No Footnotes Applicable to This Table
All tests are performed at condenser speed and indoor blower speed intended for normal operation.
NOTES:
1. Not Maintained if no condensate rejected to outdoor coil.
2. Optional test used to determine the Designed Heating Requirement (DHR). The nominal speed is the lesser of the cooling and heating maximum speeds.
3. Optional equations may be used in lieu of the maximum speed test. The intermediate speed is the same as the cooling intermediate speed.
4. Wet bulb sufficiently low that no condensate forms on evaporator.

Table 4 is reprinted from page 5 of the 1989 Standard for Unitary Air-Conditioning and Air-Source Heat Pump Equipment Standard 210/240, ARI, courtesy of the Air-Conditioning & Refrigeration Institute (ARI).


TABLE 5
Operating Conditions for Standard Rating and Performance Tests Using ASHRAE Standard 37-1988
TEST INDOOR UNIT OUTDOOR UNIT
Air Entering Air Entering Water
Air Cooled Evaporative
DB
F
WB
F
DB
F
WB
F
DB
F
WB
F
IN
F
OUT
F
C
O
O
L
I
N
G
Standard Rating Conditions Cooling1 80 67 95 752 95 75 85 95
Low Temperature Operating Cooling 67 57 67 572 67 57 - 70
Insulation Efficiency 80 75 80 752 80 75 - 80
Condensate Disposal 80 75 80 752 80 75 - 80
Maximum Operating Conditions 80 67 115 752 100 80 90 100
Part Load Conditions (IPLV) 80 67 80 672 80 67 754 -
H
E
A
T
I
N
G
Standard Rating Conditions3
(High Temperature Heating)
70 60
(max)
47 43 - - - -
Standard Rating Conditions
Low Temperature Heating (Integrated)
70 60
(max)
17 15 - - - -
Maximum Operating Conditions 80 - 75 65 - - - -
No Footnotes Applicable to This Table

Table 5 is reprinted from page 6 of the 1989 Standard for Unitary Air-Conditioning and Air-Source Heat Pump Equipment Standard 210/240, ARI, courtesy of the Air-Conditioning & Refrigeration Institute (ARI).